AQ-V211 Voltage Protection Device
Home Protection relays Voltage protection AQ-V211 Voltage Protection Device
Description
AQ-V211 offers a modular voltage protection solution for substations. The relay includes both voltage and frequency protections as well as powerful logic programming, and you can add up to five (5) I/O or communication cards. All this makes AQ-V211 optimal for demanding load shedding and automatic transfer applications. AQ-V211 communicates using various protocols, including communication according to the IEC 61850 standard.
AQ-V211 comes in two variants: the “A” variant (AQ-V211A) includes the standard functionalities for voltage protection, while the “B” variant (AQ-V211B) also includes the synchronizer function.
Configure AQ-V211A in the Product Configurator
Configure AQ-V211B in the Product Configurator
Highlights:
Eight (8) frequency stages and eight (8) setting groups for load shedding.
Synchrocheck for up to three (3) circuit breakers.
Optional synchronizer function.
Anti-islanding protection.
Technical data
AQ-V211A – Standard voltage protection functionality
AQ-V211B – Standard voltage protection functionality + Synchronizer
Overvoltage (U>; 59) - 4 stages
Undervoltage (U<; 27) - 4 stages
Neutral overvoltage (U0>; 59N) - 4 stages
Sequence voltage (U1/U2>/<; 47/27P/59PN) - 4 stages
Overfrequency and underfrequency (f>/<; 81O/81U) - 8 stages
Rate-of-change of frequency (df/dt>/<; 81R) - 8 stages
Circuit breaker failure protection (CBFP; 50BF/52BF)
Resistance temperature detectors (RTD)
Number of objects to control and monitor: 5
Number of indicators to monitor: 5
Number of setting groups: 8
Switch-on-to-fault (SOTF)
Vector jump (Δφ; 78)
Synchrocheck (ΔV/Δa/Δf; 25)
Number of objects to control and monitor: 5
Number of indicators to monitor: 5
Number of setting groups: 8
Switch-on-to-fault (SOTF)
Vector jump (Δφ; 78)
Synchrocheck (ΔV/Δa/Δf; 25)
Synchronizer (ΔV/Δa/Δf; 25)
Voltage transformer supervision (VTS; 60)
Measurement recorder
Measurement value recorder
Event recorder (max. 15,000 permanent event records)
Disturbance recorder (max. 100 records á 5 seconds at 3.2 kHz sampling)
Phase, sequence and residual voltages (UL1, UL2, UL3, UL12, UL23, UL31, U0)
Frequency (f)
Standard hardware
Voltage inputs: 4
Digital inputs: 3
Digital outputs: 5
Number of empty slots: 5
Optional hardware modules
Digital input module (8 x DI)
Digital output module (5 x DO)
Milliampere output module (4 x mA out, 1 x mA in)
RTD input module (8 RTD inputs)
Arc protection module (4 x channels, 2 x HSO, 1 x BI)
Communication media (see "Communication" below)
External I/O modules (see "Accessories" below)
Standard communication ports
RJ-45 100 Mbps Ethernet (front panel)
RJ-45 100 Mbps Ethernet and RS-485 (rear panel)
Optional communication modules
Double RJ-45 Ethernet & IRIG-B communication module
Double ST Ethernet & IRIG-B communication module
Double LC (HSR/PRP) Ethernet communication module
Double RJ-45 (HSR/PRP) Ethernet communication module
RS-232 & serial fiber communication module
Communication protocols
IEC 61850 (edition 1)
IEC 60870-5-101/104
IEC 60870-5-103
Modbus/RTU and Modbus/TCP
DNP3
SPA
AX007 External 6-channel 2-/3-wire RTD input module (pre-configured)
AX008 External 8-channel thermocouple and mA input module (pre-configured)
AX009 Raising frame (87 mm)
AX010 Raising frame (40 mm)
AX011 Combiflex frame
AX012 Wall mounting bracket