AQ-F205 Feeder Protection Device
Home Protection relays Feeder protection & control AQ-F205 Feeder Protection Device
Description
AQ-F205 is suitable for any application that requires directional overcurrent and earth fault protections along with voltage and frequency protections. AQ-F205 comes with complementary measurement, monitoring, control and communication features. The relay’s standard configuration of eleven (11) digital inputs and ten (10) digital outputs along with a large, programmable HMI allow for a variety of adaptations.
Highlights:
Integrated protection, control, and measurement.
Price–performance ratio.
Technical data
Non-directional overcurrent (I>; 50/51) - 4 stages
Non-directional earth fault (I0>; 50N/51N) - 4 stages
Directional overcurrent (Idir>; 67) - 4 stages
Directional earth fault (I0dir>; 67N/32N) - 4 stages
Negative sequence overcurrent/ Phase current reversal/ Current unbalance (I2>; 46/46R/46L) - 4 stages
Harmonic overcurrent (Ih>; 50H/51H/68H) - 4 stages
Circuit breaker failure protection (CBFP; 50BF/52BF)
High-impedance or low-impedance restricted earth fault/ Cable end differential (I0d>; 87N)
Overvoltage (U>; 59) - 4 stages
Undervoltage (U<; 27) - 4 stages
Neutral overvoltage (U0>; 59N) - 4 stages
Sequence voltage (U1/U2>/<; 47/27P/59PN) - 4 stages
Overfrequency and underfrequency (f>/<; 81O/81U) - 8 stages
Rate-of-change of frequency (df/dt>/<; 81R) - 8 stages
Overpower (P>; 32O)
Underpower (P<; 32U)
Reverse power (Pr; 32R)
Line thermal overload (TF>; 49F)
Number of objects to control and monitor: 5
Number of indicators to monitor: 5
Number of setting groups: 8
Cold load pick-up
Switch-on-to-fault
Auto-recloser (0 → 1; 79)
Synchrocheck (ΔV/Δa/Δf; 25)
Phase, sequence and residual currents (IL1, IL2, IL3, I01, I02)
Phase, sequence and residual voltages (UL1, UL2, UL3, UL12, UL23, UL31, U0)
Frequency (f)
Power (P, Q, S, pf) and Energy (E+, E-, Eq+, Eq-)
Power and energy measurement accuracy of 0.5 %
Current transformer supervision
Voltage transformer supervision (60)
Circuit breaker wear monitoring
Total harmonic distortion (current)
Fault locator (21FL)
Measurement recorder
Measurement value recorder
Event recorder (max. 15 000 permanent event records)
Disturbance recorder (max. 100 records á 5 seconds at 3.2 kHz sampling)
Current inputs: 5
Voltage inputs: 4
Digital inputs (fixed): 11
Digital outputs (fixed): 10
Standard communication ports
RJ-45 100 Mbps Ethernet (front panel, fixed)
RJ-45 100 Mbps Ethernet and RS-485 (rear panel, fixed)
Communication protocols
IEC 60870-5-101/104
IEC 60870-5-103
Modbus/RTU and Modbus/TCP
DNP3
SPA
AX007 External 6-channel 2-/3-wire RTD input module (pre-configured)
AX008 External 8-channel thermocouple and mA input module (pre-configured)
AX009 Raising frame (87 mm)
AX010 Raising frame (40 mm)
AX011 Combiflex frame
AX012 Wall mounting bracket