AQ-V251 Voltage Protection Device
AQ-V251_web
AQ-V251_web

Description

AQ-V251x offers a modular voltage protection solution for substations. The relay includes both voltage and frequency protections as well as powerful logic programming, and you can add up to thirteen (13) I/O or communication cards. All this makes AQ-V251x optimal for demanding load shedding and automatic transfer applications that require a large I/O capacity. AQ-V251x communicates using various protocols, including the IEC 61850 substation communication standard.

AQ-V251x comes in two variants: AQ-V251A has all the I/O capacity and protections, while AQ-V251B also includes the synchronizer control function.

Configure AQ-V251A in the Product Configurator Configure AQ-V251B in the Product Configurator

Highlights:

  • A large I/O capacity.
  • Eight (8) frequency stages and eight (8) setting groups for load shedding.
  • Synchrocheck for up to three (3) circuit breakers.
  • Anti-islanding protection.
AQ-V251_web

Technical data

  • Overvoltage (U>; 59) - 4 stages
  • Undervoltage (U<; 27) - 4 stages
  • Neutral overvoltage (U0>; 59N) - 4 stages
  • Sequence voltage (U1/U2>/<; 47/27P/59PN) - 4 stages
  • Overfrequency and underfrequency (f>/<; 81O/81U) - 8 stages
  • Rate-of-change of frequency (df/dt>/<; 81R) - 8 stages
  • Low-voltage ride-through (LVRT; 27T)
  • Circuit breaker failure protection (CBFP; 50BF/52BF)
  • Resistance temperature detectors (RTD)
  • Programmable stage (PSx>/<; 99)

  • Number of objects to control and monitor: 10
  • Number of indicators to monitor: 10
  • Number of setting groups: 8
  • Switch-on-to-fault (SOTF)
  • Zero sequence recloser (U0> RECL; 79N)
  • Vector jump (Δφ; 78)
  • Synchrocheck (ΔV/Δa/Δf; 25)

  • Number of objects to control and monitor: 10
  • Number of indicators to monitor: 10
  • Number of setting groups: 8
  • Switch-on-to-fault (SOTF)
  • Zero sequence recloser (U0> RECL; 79N)
  • Vector jump (Δφ; 78)
  • Synchrocheck (ΔV/Δa/Δf; 25)
  • Synchronizer (ΔV/Δa/Δf; 25)

  • Voltage transformer supervision (VTS; 60)
  • Measurement recorder
  • Measurement value recorder
  • Event recorder (max. 15,000 permanent event records)
  • Disturbance recorder (max. 100 records á 5 seconds at 3.2 kHz sampling)

  • Phase, sequence and residual voltages (UL1, UL2, UL3, UL12, UL23, UL31, U0)
  • Frequency (f)

  • Standard hardware
  • Voltage inputs: 4
  • Digital inputs: 3
  • Digital outputs: 5
  • Number of empty slots: 13
  • Optional hardware modules
  • Digital input module (8 x DI)
  • Digital output module (5 x DO)
  • High-speed high-current output module (3 x out)
  • Milliampere input module (4 x mA in, 1 x mA out)
  • Milliampere output module (4 x mA out, 1 x mA in)
  • RTD input module (8 RTD inputs)
  • Arc protection module (4 x channels, 2 x HSO, 1 x BI)
  • Communication media (see "Communication" below)
  • External I/O modules (see "Accessories" below)

  • Standard communication ports
  • RJ-45 100 Mbps Ethernet (front panel)
  • RJ-45 100 Mbps Ethernet and RS-485 (rear panel)
  • Optional communication modules
  • Double RJ-45 Ethernet & IRIG-B communication module
  • Double ST Ethernet & IRIG-B communication module
  • Double SFP Ethernet & IRIG-B communication module
  • Double LC (HSR/PRP) Ethernet communication module
  • Double RJ-45 (HSR/PRP) Ethernet communication module
  • RS-232 & serial fiber communication module
  • Communication protocols
  • IEC 61850 (edition 1)
  • IEC 61850 (edition 2)
  • IEC 60870-5-101/104
  • IEC 60870-5-103
  • Modbus/RTU and Modbus/TCP
  • DNP3
  • SPA

  • AX007 External 6-channel 2-/3-wire RTD input module (pre-configured)
  • AX008 External 8-channel thermocouple and mA input module (pre-configured)
  • AX013 Raising frame (120 mm)
  • AX014 Raising frame (40 mm)
  • AX015 Wall mounting bracket
  • AX020 SFP module (2 km, MM)
  • AX021 SFP module (40 km, SM)
  • AX022 SFP module (120 km, SM)

Additional material

Application Drawing

AQ-V251B application drawings, v1.01

Device Rear Image

AQ-251 back panel

Device and Cut-out Image

AQ 250 dimensions and cut out 2025

Order Code

V251 order code

Related products

Ask for an offer or more information

We provide a comprehensive range of services through our own skilled staff and a global network of partners.