AQ-M215 Motor Protection Device
AQ-M215_web_v3
AQ-M215_web_v3

Description

AQ-M215 offers a modular protection and control solution for larger and more important motors that require both current-based and voltage-based protection functions along with complete measurements. You can add up to three (3) I/O or communication cards into the device for more comprehensive monitoring and control applications. You can also connect up to sixteen (16) RTD signals for thermal alarming and tripping. AQ-M215 communicates using various protocols, including communication according to the IEC 61850 standard.

Highlights:

  • Powerful motor management.
  • Five (5) thermal models (time constant accurate).
  • Soft start protection beginning from 6 Hz.
  • Wye-delta started motor supervision.
  • Two-speed motor protection.
  • Optional power and energy measurement accuracy of up to 0.2 %.
AQ-M215_web_v3

Technical data

  • Non-directional overcurrent (I>; 50/51) - 4 stages
  • Non-directional earth fault (I0>; 50N/51N) - 4 stages
  • Directional overcurrent (Idir>; 67) - 4 stages
  • Directional earth fault (I0dir>; 67N/32N) - 4 stages
  • Intermittent earth fault (I0int>; 67NT)
  • Negative sequence overcurrent/ Phase current reversal/ Current unbalance (I2>; 46/46R/46L) - 4 stages
  • Harmonic overcurrent (Ih>; 50H/51H/68H) - 4 stages
  • Circuit breaker failure protection (CBFP; 50BF/52BF)
  • High-impedance or low-impedance restricted earth fault/ Cable end differential (I0d>; 87N)
  • Overvoltage (U>; 59) - 4 stages
  • Undervoltage (U<; 27) - 4 stages
  • Neutral overvoltage (U0>; 59N) - 4 stages
  • Sequence voltage (U1/U2>/<; 47/27P/59PN) - 4 stages
  • Overfrequency and underfrequency (f>/<; 81O/81U) - 8 stages
  • Rate-of-change of frequency (df/dt>/<; 81R) - 8 stages
  • Overpower (P>; 32O)
  • Underpower (P<; 32U)
  • Reverse power (Pr; 32R)
  • Motor status monitoring
  • Machine thermal overload (TM>; 49M)
  • Motor start/ Locked rotor monitoring (Ist>; 48/14)
  • Frequent start (N>; 66)
  • Mechanical jam (Im>; 51M)
  • Non-directional undercurrent (I<; 37)
  • Power factor protection (PF<; 55)
  • Resistance temperature detectors (RTD)
  • Arc protection (IArc>/I0Arc>; 50Arc/50NArc) (optional)

  • Number of objects to control and monitor: 5
  • Number of indicators to monitor: 5
  • Number of setting groups: 8

  • Current transformer supervision
  • Voltage transformer supervision (VTS; 60)
  • Circuit breaker wear monitoring
  • Total harmonic distortion (current)
  • Running hour counter
  • Measurement recorder
  • Measurement value recorder
  • Event recorder (max. 15,000 permanent event records)
  • Disturbance recorder (max. 100 records á 5 seconds at 3.2 kHz sampling)

  • Phase, sequence and residual currents (IL1, IL2, IL3, I01, I02)
  • Phase, sequence and residual voltages (UL1, UL2, UL3, UL12, UL23, UL31, U0)
  • Frequency (f)
  • Power (P, Q, S, pf) and Energy (E+, E-, Eq+, Eq-)
  • Power and energy measurement accuracy of 0.5 %
  • Power and energy measurement accuracy of up to 0.2 % (optional)

  • Standard hardware
  • Current inputs: 5
  • Voltage inputs: 4
  • Digital inputs: 3
  • Digital outputs: 5
  • Number of empty slots: 3
  • Optional hardware modules
  • Digital input module (8 x DI)
  • Digital output module (5 x DO)
  • Milliampere output module (4 x mA out, 1 x mA in)
  • RTD input module (8 RTD inputs)
  • Arc protection module (4 x channels, 2 x HSO, 1 x BI)
  • Communication media (see "Communication" below)
  • External I/O modules (see "Accessories" below)

  • Standard communication ports
  • RJ-45 100 Mbps Ethernet (front panel)
  • RJ-45 100 Mbps Ethernet and RS-485 (rear panel)
  • Optional communication modules
  • Double RJ-45 Ethernet & IRIG-B communication module
  • Double ST Ethernet & IRIG-B communication module
  • Double LC (HSR/PRP) Ethernet communication module
  • Double RJ-45 (HSR/PRP) Ethernet communication module
  • RS-232 & serial fiber communication module
  • Communication protocols
  • IEC 61850 (edition 1)
  • IEC 60870-5-101/104
  • IEC 60870-5-103
  • Modbus/RTU and Modbus/TCP
  • DNP3
  • SPA

  • AX007 External 6-channel 2-/3-wire RTD input module (pre-configured)
  • AX008 External 8-channel thermocouple and mA input module (pre-configured)
  • AX009 Raising frame (87 mm)
  • AX010 Raising frame (40 mm)
  • AX011 Combiflex frame
  • AX012 Wall mounting bracket

Additional material

Application Drawing

AQ-M215 application drawings, v1.02

Device Rear Image

AQ-215 back panel

Device and Cut-out Image

AQ210 dimensions and cut out 2025

Order Code

M215 order code